Are AFCI breakers required in an unfinished basement?
Generally no. Section 210.12(A) of the 2023 NEC lists the dwelling unit areas where 120 volt, single-phase, 15 and 20 ampere branch circuits supplying outlets or devices must have arc-fault protection: kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, and similar rooms or areas. An unfinished basement is not on that list and is not a similar room or area. GFCI protection is a different question, and the answer there is yes, because 210.8(A)(5) covers every basement receptacle.
Where the line actually falls
The trigger is the character of the space, not the floor level. A basement with framed and finished walls that gets used as a rec room, a den, a home office, or a bedroom is on the list, and every 15 or 20 ampere 120 volt circuit serving outlets in that space needs AFCI. A basement that is bare block walls, exposed joists, a furnace, a water heater, a washer and dryer, and some shop receptacles is not, with one important catch. The laundry area is explicitly on the 210.12(A) list. So if the washer and dryer sit in an otherwise unfinished basement, the laundry circuit still needs AFCI protection.
Do not forget the outlet definition
Article 100 defines an outlet as any point on the wiring system where current is taken to supply utilization equipment. That includes lighting outlets and hardwired equipment, not just receptacles. If you run a circuit from an unfinished basement panel up into a bedroom, the AFCI requirement follows the outlet, not the panel. The protection must be at the origin of the branch circuit, or you can use one of the alternative methods in 210.12(A)(1) through (A)(6), which include an outlet branch-circuit AFCI at the first outlet with a run of metal raceway or armored cable back to the panel.
Watch the shared neutral
If you have a multiwire branch circuit feeding an unfinished basement and something on the AFCI list, you cannot mix and match. A two-pole combination AFCI or two AFCI devices on a handle-tied pair is the clean answer, and 210.4(B) already requires a simultaneous disconnecting means for that multiwire branch circuit anyway.
Field takeaway
Unfinished basement general-purpose and equipment circuits: GFCI yes, AFCI no. Laundry area in that basement: both. The day the customer frames and drywalls that basement into a rec room, every 15 and 20 ampere 120 volt circuit in it needs AFCI, so if you are wiring a basement that will obviously be finished later, install the AFCI breakers now and save the callback.