Can I mount a ceiling fan to wood without a fan rated box?

The wiring still has to land in a box, and if that box is holding any part of the fan weight it has to be listed and marked for fan support. Screwing the bracket to a joist does not delete the box rule.

What 314.27(C) says

Section 314.27(C) of the 2023 NEC states that outlet boxes or outlet box systems used as the sole support of a ceiling suspended paddle fan shall be listed, shall be marked by their manufacturer as suitable for this purpose, and shall not support ceiling suspended paddle fans that weigh more than 32 kg, or 70 lb. For outlet boxes or outlet box systems designed to support ceiling suspended paddle fans that weigh more than 16 kg, or 35 lb, the required marking shall include the maximum weight to be supported.

Section 314.27(C) also requires that where spare, separately switched ungrounded conductors are provided to a ceiling mounted outlet box in a location acceptable for a ceiling suspended paddle fan, the outlet box or outlet box system be listed for the support of a ceiling suspended paddle fan. That is the rule behind fan rated boxes showing up in bedrooms during rough in.

The words sole support matter

If the fan is supported entirely by an independent structural mount, such as a bracket lagged directly to a joist or a listed hanger system, the box is not the sole support and 314.27(C) is not what governs. But you still need a box. Section 300.15 requires a box or conduit body at each outlet, and Section 314.20 requires the box to be flush or within 6 mm of the finished surface in noncombustible material, or flush in combustible material. Section 410.24 covers connection of luminaires, and Section 422.18 covers support of ceiling suspended paddle fans, requiring them to be supported independently of an outlet box or by a listed outlet box or box system identified for the use and installed per 314.27(C).

In practice, a fan mounted flat to a wood ceiling with a canopy hiding a hole in the drywall and the splices made behind the canopy with no box is a straight 300.15 violation. The splices have to be in a box, and per Section 314.29 that box has to remain accessible without removing part of the building.

Fans over 70 pounds

Section 422.18 handles the heavy fans. A ceiling suspended paddle fan over 32 kg, or 70 lb, must be supported independently of the outlet box. That means a structural mount rated for the load. The box then serves only as the wiring enclosure and carries no weight.

Field takeaway

Install a listed fan rated box. It costs a few dollars, it is faster than arguing at inspection, and it covers you if the fan is ever swapped for a heavier one. If you are mounting the fan bracket directly to structure, still bring the wiring into a listed box that stays accessible behind the canopy, and follow the manufacturer instructions under 110.3(B).